Easy Load sample sheet

Place your company information here like your company name, company phone number, company's logo, address, slogan, contracting license number, business hours, etc.
Customer Name: Mr. & Mrs. Robert Jones Heat Loss determines how much heating a room and entire building requires.
Address: 2501 Newport Heat Gain determines how much cooling a room and entire building requires.
Town: Alexander City, AL 30760 Note: Calculations are very accurate for the purpose required but are not
Phone: 888-555-1212 a perfect science because many assumptions need to be made considering
Date Prepared: 12/7/2006 the building envelope construction and materials when calculations are performed.
Preparer: Bob Wilson, Comfort Consultant
Heating Indoor Design Temp  72    Cooling Indoor Design Temperature: 76
Heating Outdoor Design Temp.    22    Cooling Outdoor Design Temp: 93
Heating Temp, Dif    50    Cooling Temperature Difference: 17
Daily Range:     M     Humidity Grains: 46
 
Note: These calculations are certified to be accurate as per industry standards 
provided by ANSI*, ASHRAE*, and ACCA Manual J* *Name trademarks held by respective entities. 
Easy LoadsTM Copyright 2008 Contractors Advantage Inc.
Certified Heat Gain Calculations 
Surface Area Kitchen Dining Breakfast Living # 1 Living # 2 Home Office Laundry Master Bedroom Master Bath Bedroom # 2 Bedroom # 3 Bedroom # 4 Hall bath Guest Bath Jack-n-Jill Bath 0
Exposed walls  0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Exposed ceiling  0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Windows & Skylights 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Doors 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Floors 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Lighting load 1,231 547 410 1,642 1,094 492 123 410 821 274 274 274 547 547 547 0
Appliance sensible load (average 800 for kitchen) 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Computer & monitor load (average 400) 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Occupant sensible load  800 800 0 800 800 0 0 0 0 0 0 0 0 0 0 0
Infiltration 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Duct gain 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Room Sensible Cooling Totals 2,031 1,347 410 2,442 1,894 492 123 410 821 274 274 274 547 547 547 0
Appliance latent load total 0
Occupant latent load  3,200
Infiltration latent load 0  
All Rooms Latent Cooling Total 3,200
All Rooms Sensible Cooling Total 12,434
Entire Home Cooling Total BTUs 15,634
Notes:
JOBSITE WORKSHEET
Site Measurements Kitchen Dining Breakfast Living # 1 Living # 2 Home Office Laundry Master Bedroom Master Bath Bedroom # 2 Bedroom # 3 Bedroom # 4 Hall bath Guest Bath Jack-n-Jill Bath  
Room Width (in .1 feet, example: 12.5) 12.5 12.5 8 19.5 12.5 17.5 8 15 5 10 15 15 12.5 10 10  
Room Length (in .1 feet, example: 15) 12 12 8 20 15 10 5 17.5 15 12 15 15 5 5 5  
If floor is above conditioned area enter 0. If not enter 1. 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1  
Ceiling height measured at outside wall 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8  
Ceiling height (averaged for sloped ceilings) 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9  
Walls above grade exposed to outside (in length)  12.5 24.5 8 19.5 27.5 27.5 0 17.5 5 0 30 30 17.5 0 5  
Walls above grade exposed to outside (in height) 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8  
Walls below grade exposed in length                                
Walls below grade exposed in height